Endress+Hauser Deltapilot Series: Hydrostatic Pressure and Level Transmitters

...
Endress+Hauser Deltapilot Series: Hydrostatic Pressure and Level Transmitters
Endress+Hauser Deltapilot Series: Hydrostatic Pressure and Level Transmitters

🛠️ Endress+Hauser Deltapilot Series: Hydrostatic Pressure and Level Transmitters

🎯 Strategic Importance of the Deltapilot Series

The Endress+Hauser Deltapilot series is a family of transmitters designed to measure the level of liquids and suitable pasty media using the hydrostatic pressure principle. These instruments support continuous level monitoring in open or closed tanks, water storage systems and wastewater applications.

In hydrostatic measurement, the sensor measures the pressure generated by the liquid column. This pressure is related to the liquid height and density:

Hydrostatic pressure:

[
p=\rho \cdot g \cdot h
]

Where:

  • p: Hydrostatic pressure generated by the liquid column

  • ρ: Liquid density

  • g: Gravitational acceleration

  • h: Liquid height

For this reason, accurate level measurement requires more than knowing the tank height. Liquid density, process pressure, measuring range and sensor installation method must also be considered.

Not all Deltapilot models have the same mechanical connection or installation arrangement. Therefore, selection should be based not only on the product family but also on the specific model and complete order code.

🔧 Deltapilot FMB50, FMB51, FMB52 and FMB53: Model Comparison

These models belong to the Deltapilot M family and use a Contite measuring cell for hydrostatic level measurement. Their main differences include mechanical design, mounting method and process connection.

Model

Basic design

Typical application considerations

FMB50

Compact pressure sensor

Level measurement applications requiring a compact design and fixed process connection

FMB51

Rod-type design

Applications using a rod-type installation with a fixed process connection

FMB52

Cable-type design with fixed process connection

Level measurement applications requiring cable-based installation

FMB53

Cable-type design with suspension clamp

Level measurement applications where the instrument is suspended using a clamp

Manufacturer product information identifies the FMB50 as a compact model, the FMB51 as a rod-type model, the FMB52 as a cable-type model with a fixed process connection, and the FMB53 as a cable-type model with a suspension clamp. Measuring ranges, process temperatures, connections and certificates must be verified for the selected variant.

📊 Technical Specifications and Measurement Limits

The manufacturer's published product information includes the following technical values for the FMB50, FMB51, FMB52 and FMB53. These values do not mean that every variant is available with the same configuration under all conditions.

Technical parameter

Value stated in manufacturer product information

Measuring principle

Hydrostatic pressure

Measuring cell

Contite

Measuring cell range

100 mbar–10 bar

Reference accuracy

Standard ±0.2%; optional ±0.1%

Maximum measuring distance

100 m H₂O

Maximum overpressure limit

40 bar

Communication options

4–20 mA HART, PROFIBUS PA or FOUNDATION Fieldbus, depending on configuration

Important technical note: The measuring cell range, the maximum permissible process pressure and the tank's measurement height are different parameters. They must not be used interchangeably. Final selection should be based on the current technical information for the relevant model and its complete order code.

🧠 Why Is the Contite Measuring Cell Important?

The Contite measuring cell used in the Deltapilot family features a hermetically sealed design that the manufacturer associates with condensation resistance and reduced effects from low temperatures.

These characteristics may be relevant in applications where ambient temperatures fluctuate or condensation is possible. However, measurement performance does not depend on sensor technology alone. Installation conditions, correct measuring range, liquid density, instrument calibration and process connection also affect the result.

The manufacturer identifies applications involving liquids and suitable pasty media, including conditions where foam may be present, among the intended uses of Deltapilot instruments. The actual application must still be evaluated against the properties of the medium and the process conditions.

🏭 Industrial Applications of the Deltapilot Series

💧 Water and Wastewater

  • Monitoring levels in storage tanks and open tanks

  • Pump stations and water collection chambers

  • Continuous level monitoring in wastewater and environmental processes

Cable-type models may be suitable where the mounting arrangement and tank design support this installation method.

🧪 Chemical and Process Industries

  • Tanks containing chemical liquids

  • Process and intermediate storage tanks

  • Applications requiring careful material compatibility assessment

For corrosive media, the materials in contact with the process, diaphragm material, seals and connection options must be checked. No material should be assumed to be compatible with every chemical.

⚡ Energy and Utility Systems

  • Water storage tanks

  • Condensate and auxiliary liquid tanks

  • Continuous liquid-level monitoring within industrial facilities

Applications involving high temperatures or special process-pressure requirements require additional verification against the instrument's limits.

🥛 Food and Hygienic Processes

For hygienic processes, the appropriate variant must be selected with the required connections, materials and certifications. The suitability of a product family for hygienic applications does not mean that every order configuration automatically carries the same hygienic approvals.

CIP/SIP suitability and requirements such as 3-A or EHEDG approval must be verified against the project specification and the selected configuration.

📐 Deltapilot Selection Criteria

The following parameters should be evaluated together when selecting a hydrostatic level transmitter.

1. Measuring Range and Tank Height

The required hydrostatic pressure depends on liquid height and density. The maximum tank height and minimum measurable level should be considered when determining the appropriate measuring range.

2. Liquid Density

If level calculations rely on an assumed or constant density, changes in density can affect the measurement result. This is particularly relevant in processes where density varies with temperature or product composition.

3. Open or Closed Tank

In open tanks, atmospheric pressure at the liquid surface generally provides the reference condition. In closed tanks, gas-space pressure can affect the measurement. The required measurement arrangement may therefore differ from a standard single-point hydrostatic measurement.

4. Process Connection and Installation

Threaded, flanged, hygienic and special connections, as well as rod-type or cable-and-suspension-clamp arrangements, must be evaluated according to the mechanical design. When replacing an existing instrument, a similar connection size alone is not sufficient to establish compatibility.

5. Medium and Material Compatibility

Wetted parts, process diaphragms, seals and, where applicable, cable materials must be compatible with the medium. Material selection should be based on the technical specification, particularly for corrosive or high-purity applications.

6. Electrical Characteristics and Communication

Power supply, output signal, control-system compatibility and communication protocol must be checked. The availability of HART, PROFIBUS PA or FOUNDATION Fieldbus must be confirmed for the selected configuration rather than assumed for every instrument.

7. Certifications and Functional Safety

Requirements such as ATEX, IECEx, SIL, drinking-water approvals or hygienic certifications must be defined for the project. Where certification is mandatory, verify the certificate and operating conditions for the exact instrument variant instead of relying solely on general product-family information.

⚠️ Installation and Commissioning Considerations

Correct installation and commissioning are as important as instrument selection for achieving reliable measurement performance.

  • Installation position: Confirm that the sensor is installed in accordance with the tank geometry and process connection.

  • Measuring range: Ensure that the level range, measured pressure and control-system scaling are consistent.

  • Density setting: Where pressure is converted into level units, verify that the density value used matches the process conditions.

  • Electrical connection: Check the power supply, signal wiring, grounding and communication settings according to the relevant instrument manual.

  • Calibration and zero point: During commissioning, account for the actual installation conditions and follow the manufacturer's instructions.

  • Certification requirements: In Ex or functional-safety applications, installation and commissioning must comply with the applicable standards and instructions.

🔄 Replacement, Legacy Products and Order Code Verification

When replacing an existing Deltapilot instrument or sourcing an older model, a decision should not be made solely on the basis of the FMB50, FMB51, FMB52 or FMB53 model name.

The following details should be compared during replacement and cross-reference evaluations:

  1. Complete order code and existing instrument nameplate information

  2. Measuring range and calibrated range

  3. Process connection and mechanical mounting arrangement

  4. Wetted materials and seal options

  5. Output signal, communication protocol and power supply

  6. Process temperature, pressure limits and ambient conditions

  7. Required Ex, SIL, hygienic or other certifications

  8. Compatibility with the control system and existing wiring

Important: Models within the same product family may have different mounting arrangements and connection designs. Compatibility with a newer model must not be assumed until the complete order code and technical documentation have been compared. Product availability and current alternatives should also be verified separately.

📋 Information Required for an RFQ

When requesting a quotation or alternative-product assessment for a Deltapilot instrument, providing the following information helps facilitate the evaluation:

  • Model name and complete order code, if available

  • Photograph of the instrument nameplate

  • Required quantity

  • Measuring range and application details

  • Process connection and material requirements

  • Output signal and communication protocol

  • Required certifications

  • Project country and delivery expectations

If the existing order code is unavailable, a nameplate photograph, technical specification or documentation for the installed instrument can provide a starting point. Missing information should be identified clearly so that technical verification can be carried out appropriately.

❓ Frequently Asked Questions

What measuring principle does Deltapilot use?

Deltapilot measures the hydrostatic pressure generated by a liquid column to determine liquid level. Accurate level calculation requires consideration of liquid density and application conditions.

What is the main difference between FMB50, FMB51, FMB52 and FMB53?

The main differences concern mechanical design and mounting arrangement. The FMB50 is a compact model, the FMB51 is rod-type, the FMB52 is a cable-type model with a fixed process connection, and the FMB53 is a cable-type model with a suspension clamp. Final selection should be verified against current technical documentation and the order code.

Do Deltapilot models support HART or fieldbus communication?

Manufacturer product information lists 4–20 mA HART, PROFIBUS PA and FOUNDATION Fieldbus options. However, the supported protocol depends on the selected instrument variant. It should not be assumed that every model supports every protocol.

Is the model name alone sufficient when replacing a Deltapilot instrument?

No. The complete order code, measuring range, process connection, materials, electrical characteristics and required certifications must be checked together.

✅ Conclusion

The Endress+Hauser Deltapilot series offers different mechanical designs and mounting options for hydrostatic liquid-level measurement. Selecting the appropriate FMB50, FMB51, FMB52 or FMB53 model depends on tank design, measuring range, liquid properties, process connection and control-system requirements.

For technically sound selection and reliable replacement assessment, the model name alone is insufficient. Current technical documentation, the complete order code and actual application requirements must be verified together.

📩 Deltapilot Sourcing and Technical Product Verification

Yeşil Grup Enerji is not an official distributor or authorized representative of Endress+Hauser. As an independent, brand-independent industrial supplier, we can support customers with:

  • Deltapilot model and complete order code verification

  • Alternative-product research for legacy instruments

  • Technical documentation and configuration comparison

  • Cross-reference research and global sourcing

  • RFQ management and project-specific quotation support